SD10000RTL, 10kVA/10kW, RT4U, LCD, USB, external battery, terminal in&out 2E-SD10000RTL
In view of the military present, the source of uninterrupted power supply of 2E brand is a must-have for business and the stable functioning of critical public institutions, in particular, maternity hospitals, laboratories, etc. The model has a power of 10 kW. 2E SD10000RTL type: online double conversion. UPS of this class provide the most reliable protection of the connected equipment against interruptions in the power grid, which undoubtedly compensates for the costs of its purchase and installation.
Device type | double conversion |
Mounting type | classic (tower) / rack mount |
Оptions | SNMP-adapter |
THDi | ≤ 5% |
Input | Single-phase three-wire (1F + N + PE) |
Input voltage | 110-176 V (linear decrease in performance between 50% and 100% load) / 176 - 288 V (without performance degradation) |
Input frequency | 40-70 (автоматичне визначення) |
Output | Single phase (1F + N) |
Output voltage | 220 V / 230 V / 240 V / 208 V |
Max. Output Power | 10000 VA |
Effective Output Power | 10000 V |
Output frequency | 50-60 ± 0,1% |
Type of output power | Terminal block |
Power factor | 1 |
Without internal batteries | 1 |
Maximum battery charge current | 5 |
Overload | 105% - 110% for 10 min / 110% - 125% for 1 min / > 126% - 150% for 30 s |
Efficiency | ≥ 94% at 100% load |
Connecting an external battery | 1 |
Protection | Short circuit protection / Overload protection / deep discharge protection / overheat protection / fan check |
Interface | USB / RS-232 / optional SNMP adapter |
Display | 1 |
Operating temperature | 0-40 °C |
Relative humidity | 0-95% (non-condensing) |
Colour | black |
Dimensions ( HxWxD ) | 88x440x580 |
The weight | 14 kg |
The operation principle is that the input AC voltage is converted by the rectifier into DC, and then by the inverter – back into AC. Even in the presence of large deviations in the input voltage, 2E UPS continues to supply the connected devices with a pure sinusoidal stabilized voltage. The lack of switching between modes (mains to battery) allows to minimize the risk of damage to «sensitive» equipment. In particular, such UPSs are used for uninterrupted power supply of medical equipment, for data centers and enterprises with a continuous production cycle. The input voltage range is: 110 ~ 176 VAC (linear derating between 50% and 100% load); 176 ~ 288 VAC (no degradation). Input: single-phase three-wire (1F + N + PE). Output: single-phase (1F + N), adjustable voltage 208/220/230/240 V is provided.
The operating frequency range of 2E SD10000RTL model is within 40 ~ 70 Hz (automatic detection).
This UPS does not have internal batteries, instead you can use external 16-20 pcs., 12 V, 9 Ah.
In addition, various RS-232, USB and an optional SNMP adapter are provided. A multi-function LCD display built into the front panel displays the device’s operating status, including error codes.
With a weight of 14 kg, the device has dimensions of 440 × 580 × 88 mm. Installation type: universal (RACK/TOWER). The noise level is 58 dB. The product has IP20 protection degree, as well as protection against short circuit, overload, overheating, full battery discharge and fan check ability. ECO mode and microprocessor control are available.
Withstands overload up to 150% for 30 seconds.